Emergency Backup
Operation
0: In TEST mode, the load will not be transferred
to the genset even if the mains fail.
1: In TEST mode, the load will be transferred to
the genset if the mains fail.
0: No modem connection, the serial port is
connected to PC
0: RAINBOW communication protocol.
1-144: MODBUS communication. This parameter
is also the MODBUS controller address of the unit.
This parameter controls SMS sending when mains
voltages status is changed. No warning is
generated.
0: no SMS when mains failed or restored
1: SMS sent when mains failed or restored
Fuel Consumption per
Hour
This parameter is the threshold for sending FUEL
THEFT and FUELLING sms messages.
If this parameter is set to 0, then no Fuel Theft and
Fuelling sms messages will be sent.
If SMS is required, set this parameter to a value
above the hourly fuel consumption of the genset.
This parameter trims precisely the real time clock
circuit.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
0: no Remote Start signal
1: SPARE-2 input is Remote Start signal
0: no Simulate Mains signal
1: SPARE-2 input is Simulate Mains signal
0: The SPARE-2 input has normal function
1: The SPARE-2 input has delayed simulate
mains function. See chapter 6.8 for more info.
Delayed Simulate Mains Operation: max
genset running time after Simulate Mains signal
disappears.
Dual Genset Systems: flashing relay toggle
timer. Please contact DATAKOM for dual genset
mutual stanby operation.